Product Overview
The CY-LRSGD filter reactor is suitable for reactive power compensation and harmonic management systems. The filter reactor is connected to the capacitor and uses LC resonance physical characteristics to generate the minimum or maximum impedance. It absorbs or blocks the harmonic voltage and current at the corresponding frequency in the power grid, achieving the goal of harmonic filtering and maintaining the optimal value of the system power factor, effectively improving the power quality of the power grid.
Usage conditions
Environmental temperature: -25~+40 ℃; Relative temperature ≤ 90% RH
Altitude: not exceeding 2000m
No severe vibration and impact, no flammable and explosive hazardous materials, no conductive dust
There should be good ventilation conditions around, such as ventilation facilities inside the loading cabinet
Temperature resistance level H (180 ℃) or above
Technical parameter
Can be used in systems such as 400V, 660V, 690V, etc
Tune frequency points: different frequencies such as 150Hz, 250Hz, 350Hz, 550Hz, etc
Rated insulation level 3kV/min
The maximum temperature rise of each part of the reactor, with the winding not exceeding 80K and the iron core not exceeding 95K
The noise of the reactor shall not exceed 45dB
The difference in reactance values between any two phases of a three-phase reactor shall not exceed 3%
Capable of long-term operation at power frequency and harmonics greater than 1.35 times the rated current
Application occasions
The strong current harmonic power supply system can filter out higher-order harmonics and compensate for system power factor.